ტექნიკური პარამეტრები 2E GDC, 12V, 200Ah, GEL:
მთავარი მახასიათებლები
მთავარი მახასიათებლების სრული სია
A type GEL VRLA
Rated voltage 12 V
The nominal capacity 200 Ah (С10)
Тип электролита GEL
Maximum discharge current 1600 A (5 second)
The weight 62 kg (можливе відхилення ваги – до 5%)
Dimensions (LxWxH) mm 240 x 523 x 219
Main characteristics
A type GEL VRLA
Rated voltage 12 V
The nominal capacity 200 Ah (С10)
Maximum charge current 40A
Type of terminals М8
Number of charge-discharge cycles D.O.D. 30% - до 1200 циклов
D.O.D. 50% - до 600 циклов
D.O.D. 100% – до 300 циклов
Тип электролита GEL
Additionally
Maximum discharge current 1600 A (5 second)
The optimum operating temperature 25°C±3°C
+15°С-+25°С /рекомендуемый диапазон температур эксплуатации
Self-discharge at 20°C (% per month) 3
Емкость батареи (для С10) 102% +40°C
85% 0°C
65% -15°C
Physical characteristics
Life time 5 years /в буферном режиме
Colour black
The weight 62 kg (можливе відхилення ваги – до 5%)
Dimensions (LxWxH) mm 240 x 523 x 219
შეფუთვის პარამეტრები
სიგანე 260 მილიმეტრი
სიმაღლე 270 მილიმეტრი
სიგრძე 530 მილიმეტრი
წონა 62.50 კგ
მოცულობა 0.0372 მ3
გარანტია
გარანტია 12 თვე
In a world where a stable power supply is critical for security, IT infrastructure, and industrial processes, choosing a high-capacity battery is an investment in peace of mind. The 2E GDC 12V 200 Ah battery has been designed with this philosophy: maximum reliability, long service life, and full compliance with the requirements for buffered operation.
1343 ლარი*
ხელმისაწვდომია
 
* საშუალო ფასი ბაზარზე
GEL Technology: Stability Without Compromise

This model belongs to the VRLA (Valve Regulated Lead Acid) class but uses a gel electrolyte, significantly improving its performance characteristics. The GDC series batteries use AGM-GEL technology, providing high resistance to deep discharge, minimizing the risk of plate degradation, and ensuring safe, sealed, maintenance-free operation. These batteries are perfect for powering IT and telecommunications equipment, data centers, and are the best choice for solar and wind power stations and off-grid energy systems. The GDC batteries comply with IEC60896-21/22 (for stationary installations) and IEC61427-1/2 (for photovoltaic solar systems) standards.

Maximum Energy Density in a Convenient Form Factor

With a capacity of 200 Ah (C10), the battery provides long-lasting power for critical systems. Its maximum discharge current reaches 1,600 A (for 5 seconds), ensuring system startup even under sudden peak loads. The maximum charging current is 40 A, guaranteeing efficient recharge without the risk of overheating or shortening the battery’s lifespan.

Despite its 62 kg weight (±5% deviation), the battery maintains compactness for its class, with dimensions of 219 × 523 × 240 mm, allowing it to be integrated into standard enclosures and cabinets. The package includes M8 bolts for connections.

Lifespan of up to 15 Years: Durability with Consideration of Cycling

In buffered operation mode, the battery will work for up to 10 years but can also withstand a moderate number of charge/discharge cycles. It is important to note that the depth of discharge (DOD) directly affects the lifespan of the battery:

  • At 30% DOD: up to 1,200 cycles
  • At 50% DOD: up to 600 cycles
  • At 100% DOD: up to 300 cycles

This shows that GEL technology is effective for buffered use but is not intended for frequent deep discharges. Therefore, the battery is not recommended for use in off-grid or mobile systems, where cycling is constant.

Temperature Parameters: Adaptive Performance

The recommended temperature range for operation is +15°C to +25°C, as it provides the highest stability and longevity for the battery. However, it remains functional even under more extreme conditions. The capacity varies depending on the temperature:

  • 102% at +40°C
  • 85% at 0°C
  • 65% at -15°C

This performance profile makes the battery versatile for use in indoor environments, technical rooms, and telecommunications systems.

 Adhering to Guidelines for Long-Term Operation

Despite its high potential, it is essential to adhere to the recommended operating conditions:

  • Do not use the battery outside the recommended mode.
  • Always fully recharge the battery after discharge.
  • Calculate the overall system capacity according to the battery class and load specifications.

It is also important to consider the self-discharge rate, which is only 3% per month at 20°C, ensuring long service life without loss of functionality.

 

  • GEL (VRLA) Technology
  • Capacity: 200 Ah (C10)
  • Service life up to 15 years in buffered operation mode
  • Discharge current: 1,600 A for 5 seconds
  • Maximum charge current: 40 A
  • M8 terminal (bolts for connections included)
  • Cycle life at different depths of discharge (DOD): 30% DOD: up to 1,200 cycles, 50% DOD: up to 600 cycles, 100% DOD: 300 cycles
  • Operating temperature range: -15°C to +40°C, optimal range: +15°C to +25°C
  • Capacity depending on ambient temperature: 102% at +40°C, 85% at 0°C, 65% at -15°C
  • Low self-discharge rate: 3% per month at 20°C
  • Compliant with IEC60896-21/22 and IEC61427-1/2 standards
  • Dimensions: 219 × 523 × 240 mm
  • Weight: 62 kg (±5%)